Control via the operator panel
4.7 Sprachauswahl/Language selection menu
Cabinet Modules Operator Panel AOP30
Operating Instructions, 04/2014, A5E03263551A
57
4.7
Sprachauswahl/Language selection menu
The operator panel downloads the texts for the different languages from the drive.
You can change the language of the operator panel via the "Sprachauswahl/Language
selection" menu.
Note
Additional languages for the display
Languages in addition to the current available languages in the display are available on
request.
4.8
Operation via the operator panel (LOCAL mode)
You activate the control keys by switching to the LOCAL mode. If the green LED in the
LOCAL/REMOTE key does not light up, the key is not active.
Note
If the "OFF in REMOTE" function is activated, the LED in the LOCAL-REMOTE key flashes.
All of the supplementary setpoints are deactivated for LOCAL master control.
After the master control has been transferred to the operator panel, the BICO
interconnections at bit 0 to bit 10 of the control word of the sequence control are not effective
(refer to function diagram 2501).
Note
If STARTER has the master control, then when the LOCAL-REMOTE button is pressed, the
"Other device has master control" message is output and transfer of master control is
rejected.