Control via the operator panel
4.8 Operation via the operator panel (LOCAL mode)
Cabinet Modules Operator Panel AOP30
Operating Instructions, 04/2014, A5E03263551A
61
4.8.7
Lock AOP LOCAL Mode
Settings: Menu – Commissioning/Service – AOP settings – Control settings
Inhibit AOP LOCAL mode (factory setting: No)
●
Yes: Deactivates the "Control via operator panel" function, thereby disabling the
LOCAL/REMOTE key.
●
No: Activates the LOCAL/REMOTE key.
Note
Lock LOCAL
LOCAL functionality can also be inhibited on the drive by means of the p0806 parameter (BI:
Inhibit master control).
4.8.8
Acknowledge error from the AOP
Settings: Menu – Commissioning / Service – AOP Settings – Control Settings
Acknowledge error from the AOP (factory setting: yes)
●
Yes: Errors can be acknowledged via the AOP.
●
No: Errors cannot be acknowledged via the AOP.
4.8.9
CDS setting via AOP
Settings: Menu – Commissioning/Service – AOP settings – Control settings
CDS changeover via AOP (factory setting: No)
●
Yes: In the LOCAL mode, the active CDS be changed by one in the operating screen
form. This is helpful if operation via the AOP would not be possible due to the fact that a
standard telegram has been activated.
When CDS0 or 2 is active, "CDS+1" switches to CDS1 or CDS3.
When CDS1 or 3 is active, "CDS-1" switches to CDS0 or CDS2.
●
No: In the LOCAL mode, the active CDS cannot be changed by one in the operating
screen form.
4.8.10
Timeout monitoring
In "LOCAL" mode or if "OFF in REMOTE" is active, the drive is shut down after 1 s if the data
cable between the AOP and drive is disconnected.