105/138
Siemens
User Manual
CE1U2353en
Building Technologies
Configuration
2014-07-30
Sensor state
Line no.
Operating line
6200
Save sensors
At midnight, the basic unit stores the states at the sensor terminals.
If, after storage, a sensor fails, the basic unit generates an error message.
This setting is used to ensure immediate saving of the sensors. This becomes a
requirement when, for instance, a sensor is removed because it is no longer needed.
Parameter reset
Line no.
Operating line
6205
Reset to default parameters
All parameters can be set to their default values. Exempted from this are the following
operating pages:
Time of day
and
date
,
operator unit
,
radio and all time programs
,
as well the s
etpoint manual control
.
Plant diagram
Line no.
Operating line
6212
Check-No. heat source 1
6215
Check-No. storage tank
6217
Check-No. heating circuits
To identify the current plant diagram, the basic unit generates a check number.
The check number is made up of the lined up part diagram numbers.
Every control number consists of 3 columns, each representing the application of a
plant component. Every column shows a number with a maximum of 2 digits. Exception
is the first column. If the first digit in the first column is a 0, the 0 will be hidden.
Operating
line
First column
2 digits
Second column
2 digits
Third column
2 digits
BZ6212
Solar
BZ6215
DHW storage tank
BZ6217
Heating circuit P
Heating circuit 2
Heating circuit 1
Solar
Oil / gas boiler
0
No solar
00 No
boiler
1
Solar with collector sensor
and pump
DHW storage tank
0
No DHW storage tank
1
electric immersion heater
2
Solar connection
4
Charging pump
5
Charging pump, solar
connection
13 Diverting
valve
14
Diverting
valve,
solar
connection
Structure of control
number
Check-No. heat source 1
Check-No. storage tank
RVS46.543 only