
85/138
Siemens
User Manual
CE1U2353en
Building Technologies
DHW
2014-07-30
No priority
DHW heating and space heating take place at the same time.
In the case of tightly sized heat generators and mixing heating circuits, it can occur that
the DHW setpoint will not be reached if space heating calls for considerable amounts of
heat.
Mixing heating circuit shifting, pump heating circuit absolute
The pump heating circuits stay locked until the DHW storage tank is heated up. If the
capacity of the heat source is not sufficient, the mixing heating circuits will also be
restricted.
Legionella function
Line no.
Operating line
1640
Legionella function
Off
Periodically
Fixed weekday
1641
Legionella funct periodically
1642
Legionella funct weekday
Monday…Sunday
1644
Legionella funct time
1645
Legionella funct setpoint
1646
Legionella funct duration
1647
Legionella funct circ pump
·
Periodically
The legionella function is repeated according to the period of time set (operating line
1641). The legionella setpoint is attained via a solar plant, independent of the period of
time set, the period of time will be newly started.
·
Fixed weekday
The legionella function can be activated on a fixed weekday (operating line 1642).
When using this setting, heating up to the legionella setpoint takes place on the
selected weekday, independent of previous storage tank temperatures.
During the time the legionella function is carried out, the DHW circulating pump can be
activated.
During the time the legionella function is carried out, there is a risk of scalding when
opening the taps.
Circulating pump
Line no.
Operating line
1660
Circulating pump release
Time program 3/HCP
DHW release
Time program 4/DHW
Time program 5
1661
Circulating pump cycling
1663
Circulation setpoint
When the function is activated, the circulating pump is switched on for 10 minutes
within the release time and then switched off again for 20 minutes.
If a sensor is installed in the DHW distribution pipe, the controller will monitor its actual
value during the time the legionella function is performed. The adjusted setpoint must
be maintained at the sensor during the adjusted “Dwelling time“.
Legionella function
Legionella funct circ pump
Circulating pump cycling
Circulation setpoint
RVS46
.543
only
RVS46.543 only
RVS46.543 only
RVS46.543 only