Instantaneous DHW heater
2014-07-30
External thermostat
The storage tank is charged with an external thermostat without setpoint compensation
of the controller.
DHW sensor
The storage tank is charged with an electric immersion heater, with setpoint
compensation from the controller.
To ensure that setpoint compensation operates as required, the external control
thermostat must be set to the minimum storage temperature.
Excess heat draw
Line no.
Operating line
5085
Excess heat draw
Off
On
Excess heat draw can be triggered by the following functions:
-
Inputs H1, H2, H3 or EX2
-
Storage tank recooling
-
Solid fuel boiler excess heat draw
When dissipation of excess heat is activated, it can be drawn by space heating. This
can be adjusted separately for each heating circuit.
Plant hydraulics
Line no.
Operating line
5090
With buffer storage tank
5092
With prim contr/system pump
5093
With solar integration
If there is a buffer storage tank, specify whether the DHW storage tank can draw heat
from it.
When using alternative heat sources, the buffer storage tank temperature is used as a
control criterion for the release of additional heat sources.
It is to be set whether the DHW storage tank receives its heat via the primary controller
or with the help of the system pump (depending on the type of plant).
It is to be set whether the DHW storage tank receives its heat from the solar collectors.
6.13 Instantaneous DHW heater
Mixing valve control
Line no.
Operating line
5544
Actuator running time
Setting the running time of the actuator used with the mixing valve.
El immersion heater
control
Excess heat draw
With buffer storage tank
With primary controller /
system pump
With solar integration
Actuator running time
RVS46.543 only