![Siemens Add 7 AddFEM Manual Download Page 62](http://html.mh-extra.com/html/siemens/add-7-addfem/add-7-addfem_manual_377066062.webp)
AddFEM
Technical Data
4-11
AddFEM
C79000–G8076–C900–03
Analog Outputs
Number of analog outputs
8
Greatest error at 25
°
C
$
0.15%
Temperature coefficient
$
100 ppm/K
Greatest error across the complete
temperature range
$
0.4%
Digital resolution of the digital–analog
converter
13 bits + preceding sign
Value of the least significant bit (LSB)
8
µ
A
Total system transfer time interval
(TAQD +TAQT)
1 ms
Transient recovery time at changes
across the entire range
0.6 ms
Overshoot
0.2%
Greatest temporary deviation during
each specified electrical disturbance
test
Refer to EMC data (Section 4.2)
Configuration of the terminals
Refer to Appendix A, connector X4,
Page A-1
Permissible inductive load
1 H
Shutdown cycles of the power supply
Up to 10 ms a buffer overrides.
In case of longer failures the starting
operation depends on the software
Conversion process
Parallel conversion of all 8 output
channels
Power output range unipolar / over-
flow range / load impedance
0...20 mA/
$
23.5 mA/500
Ω
4...20 mA/–4.96 to +22.96 mA/500
Ω
Power output range bipolar / overflow
range / load impedance
"
20 mA/
"
23.5 mA/500
Ω
"
30 mA/
"
35.55 mA/300
Ω
Power output bipolar (only channels 1
to 4)
1)
"
50 mA/
"
59.26 mA/180
Ω
Monitoring tolerance of the output cur-
rent
4%
Feedthrough between the channels
at:
Direct voltage
50 Hz
60 Hz
v
60 dB
v
60 dB
v
60 dB
Non–linearity
t
0.1%
Output ripple
t
0.1%
1)
The analog outputs 1 to 4 are limited to a mean load of 40 mA in order to
protect the module. The extension of the current range of these outputs to 50
mA / 59.26 mA is only intended for controlling integral–action actuating ele-
ments. To this purpose a max. current of 59.26 mA is provided for a limited
period.
The current is monitored by software and is limited as follows:
Mean–value limitation: At a power output configured to
"
50 mA a first–order
time delay with a time constant of 10 seconds is used to form the mean value
of the output current. It the mean value exceeds a current of 40 mA, the out-
put current and thus also the mean value of the output current is limited to
"
40 mA.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for Add 7 AddFEM
Page 7: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Page 27: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Page 51: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Page 81: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...