23
Button Functions in Display Mode
Reset Mode
In Reset mode, you can perform a Current (Maximum) Demand reset, a
Power (Maximum) Demand reset, or an Energy reset.
Perform a Power (Maximum) Demand Reset to reset these registers:
Real Power Demand Maximum; Reactive Power Demand Maximum; or
Apparent Power Demand Maximum.
For revenue sealed meters, Energy resets are not permitted.
Button Functions in Reset Mode
Configuration Mode
In Configuration mode, first use the buttons to locate the parameter to be
edited (Configuration Select mode), then use the buttons to edit the displayed
parameter (Configuration Edit mode).
Configuration Select mode: locate a displayed parameter that requires
editing by pressing the Up or Down button.
Mode
Button
Function
Display
Mode
Display
mode is
the meter
default.
View the previous parameter value.
View the next parameter value.
Move from one measurement group to the next measurement
group.
Screen
String
Current Maximum Demand Reset
Power Maximum Demand Reset
Energy Reset
rr
r
EnEr
Mode
Button
Function
Reset Mode
ENTER Reset mode
by pressing the Enter button
and holding for
2 seconds.
EXIT Reset mode with the
same button sequence.
View the previous reset parameter.
View the next reset parameter.
Program the selected (flashing) parameter
reset to the meter.