20
Notes
1
For a meter with the Megawatt option, PTS must be set to “x1000.”
2
ION compatible protocol for use with an WinPM.Net system and
other ACCESS meters.
3
The units displayed on the front panel are Wh, VAh, and VARh with actual
values of kWh, kVAh, and kVARh respectively.
kWh REc. and kVARh Rec. are represented by a lit “minus” (negative
value) LED.
4
In Ext 1 or Ext 2 mode, the digital outputs are reserved for digital control.
5
Time Constant, sometimes called kT, is the number of units (kWh, kVAh,
kVARh) per output transition. The digital output uses KY pulsing. This
means that the relay changes from open to closed or from closed to open
whenever kT units have been measured (20 transitions/second maximum).
Mo
dbus
Sca
lin
g
Voltage Scale
0.001, 0.01, 0.1, 1, 10, 100,
1000
10
Current Scale
0.001, 0.01, 0.1, 1, 10, 100,
1000
10
Power Scale
0.001, 0.01, 0.1, 1, 10, 100,
1000
1
Neutral Scale
0.001, 0.01, 0.1, 1, 10, 100,
1000
10
Di
gita
l O
utpu
ts
Output Mode Digital
#1
(k)Wh Del., (k)VAh, (k)VARh Del.,
(k)Wh Rec., (k)VARh Rec. See note
3
Ext 1
4
, Ext 2
4
(k)Wh
3
Time Constant 1 (kT)
5
0.1 – 999.9
(only 1 digit after the decimal pt.
permitted)
1.0
Output Mode Digital
#2
(k)Wh Del., (k)VAh, (k)VARh Del.,
(k)Wh Rec., (k)VARh Rec. See note
3
Ext 1
4
, Ext 2
4
(k)VARh
3
Time Constant 2 (kT)
5
0.1 – 999.9
(only 1 digit after the decimal pt.
permitted)
1.0
Di
sp
la
y
Display Scroll Time
0 – 30 seconds (0 = disable)
0
Display Refresh Period
1 – 6 seconds
2
Se
curi
ty
Password
0 – 9999
0
String
Description
Range (Values)
Default
PUS
PCS
PCS
PPS
PPS
PnS
PnS
out1
out1
tc1
tc1
out2
out2
tc2
tc2
dS r
c
dUPd
dUPd
PSEt