Power Supply Connections
Step 8: Power Up the Meter
1.
Close the PT fuses (or direct voltage input fuses).
2.
Open the CT shorting blocks.
3.
Apply power to the meter.
Step 9: Set Up the Meter Using the Front Panel
See “Configuration Mode” on page 23, in the “Using the Meter” section, for
detailed instructions on setting up the meter.
The following settings can be configured on your meter using the front panel.
Power Supply
Connector Type
Wire
Standard AC / DC power supply
Captured wire
18 to 14 AWG
(0.8mm
2
to 2.1mm
2
)
Low Voltage DC power supply
Captured wire
18 to 14 AWG
(0.8mm
2
to 2.1mm
2
)
480 V power supply
Ring
Split-ring
Bare wire
18 to 14 AWG
(0.8mm
2
to 2.1mm
2
)
G L+ N-
2A fuse on L+ and N-
DO NOT install the N- fuse in a
grounded neutral power system
480V Power Supply
Standard AC/DC and
Low Voltage DC Power Supply
100 mA fuses on
L1 and L2
Connections to the
L1 and L2 terminals
can come from V1
and V2