Operating instructions
7SV512
V1
C53000---G1176---C91
92
6.4.5 Read-out of operational measured values --- address block 57
The steady state rms operating values can be read
out at any time under the address 5700. The ad-
dress can be called up directly using
DA 5 7 0 0 E
or by paging with
Ý
or
ß
. The individual measured
values can be found by further paging with
"
or
#
.
Entry of the codeword is not necessary. The values
are updated in approximately 5 seconds intervals.
The data are displayed in absolute primary values
and in percent of the rated device values. To ensure
correct primary values, the rated data must be en-
tered to the device under address block 11 as de-
scribed in Section 6.3.3.
In the following example, some typical values have
been inserted. In practice the actual values appear.
Values outside the operation range of the relay are
indicated with
KKKK
.
5 7 0 0
O P E R A T I O N A L
M E A S U R E D
V A L U E S
Beginning of the block ”Operational measured val-
ues”
Use
"
key to move to the next address with the next measured value.
5 7 0 1
M E A S . V A L U E
I L 1
= 3 8 5
A
Page on with the
"
key to read off the next address
with the next measured value, or page back with
#
.
One address is available for each measured value.
The values can be reached also by direct addressing
using key
DA
followed by the address number and
execute with
E
.
The primary values (addresses 5701 to 5704) are re-
lated to the primary rated values as parameterized
under address 1105 (for I
N
) (refer to Section 6.3.3).
The percentage is related to rated current of the relay
5 7 0 2
M E A S . V A L U E
I L 2
= 3 8 2
A
5 7 0 3
M E A S . V A L U E
I L 3
= 3 8 6
A
5 7 0 4
M E A S . V A L U E
I E
= 1
A
5 7 1 0
M E A S . V A L U E
I L 1 [ % ] = 9 6 . 2
%
5 7 1 1
M E A S . V A L U E
I L 2 [ % ] = 9 5 . 5
%
5 7 1 2
M E A S . V A L U E
I L 3 [ % ] = 9 6 . 5
%
5 7 1 3
M E A S . V A L U E
I E [ % ]
= 0 . 2
%