Technical data
7SV512
V1
C53000---G1176---C91
20
3.1.4 Climatic stress tests
--- Permissible ambient temperature
during service
---5
C to +55 C
during storage
---25 C to +55 C
during transport
---25 C to +70 C
Storage and transport with standard works packaging!
--- Permissible humidity
mean value per year
±
75 % relative humidity;
on 30 days per year 95 % relative humidity;
Condensation not permissible!
We recommend that all units are installed such that they are not subjected to direct sunlight, nor to large tem-
perature fluctuations which may give rise to condensation.
3.1.5 Service conditions
The relay is designed for use in industrial environ-
ment, for installation in standard relay rooms and
compartments so that with proper installation
elec-
tro-magnetic compatibility (EMC)
is ensured. The
following should also be heeded:
--- All contactors and relays which operate in the
same cubicle or on the same relay panel as the
digital protection equipment should, as a rule, be
fitted with suitable spike quenching elements.
--- All external connection leads in sub-stations from
100 kV upwards should be screened with a
screen capable of carrying power currents and
earthed at both sides. No special measures are
normally necessary for sub-stations of lower volt-
ages.
--- It is not permissible to withdraw or insert individu-
al modules under voltage. In the withdrawn condi-
tion, some components are electrostatically en-
dangered; during handling the standards for
electrostatically endangered components must
be observed. The modules are not endangered
when plugged in.
WARNING! The relay is not designed for use in resi-
dential, commercial or light-industrial environment
as defined in EN 50081.
3.1.6 Design
Housing
7XP20; refer Section 2.1
Dimensions
refer Section 2.2
Weight (mass)
--- in housing for surface mounting
approx 11.0 kg
--- in housing for flush mounting
approx 9.5 kg
Degree of protection acc. to EN 60529
--- Housing
IP 51
--- Terminals