Test procedure
1. The customer selects cables or conductors by random sampling.
2. The following is inspected:
– Are the cables firmly connected?
– Have edge protectors been attached to sharp edges?
– Are the cables routed according to the circuit diagram?
Result
The inspection is passed if the cable installation does not exhibit any deficiencies and matches
the information in the circuit diagram.
3.1.5
Cable markings
Fundamentals
A visual inspection is made to see whether cables and conductors are marked as defined in the
circuit diagram.
Test procedure
1. The customer selects cables or conductors by random sampling.
– Are the cable end tags and conductor colors of cables and conductors marked as defined
in the circuit diagram?
Result
The test is passed if the cable and conductor markings match what is specified in the circuit
diagram.
3.1.6
Setting values of circuit breakers, if used
Fundamentals
The circuit breaker settings are visually checked against what is specified in the circuit diagram.
Test procedure
1. The customer selects circuit breakers by random sampling.
2. The circuit breaker settings are visually checked against what is specified in the circuit
diagram.
Tests
3.1 Visual inspection
SINAMICS SL150 6SL3860 F03 F70 F98 F79 F76
20