8.5.1
External warnings and faults
With the terminal blocks TM15/TM31, there are 24 terminals. With STARTER or SCOUT, you
can select which predefined messages are displayed and which protection devices are to be
triggered. The list of parameterized faults and alarms can be found in the List Manual in the
"Faults and alarms" section.
8.5.2
Diagnostics
8.5.2.1
Diagnostics via LEDs
LEDs of the Sirius safety relay
Table 8-1
LEDs of the Sirius safety relay
LED
Operation
POWER
CHANNEL1
CHANNEL2
Line supply
EMERGENCY
STOP
ON
Release circuits
☀
☀
☀
On
Not actuated
Actuated
Closed
☀
○
○
Actuated
Not actuated Open
☀
○
○
Not actuated
Not actuated Open
Fault
☀
○
○
● Relay jammed
● Motor contactor jammed
● Defect in electronics
Open
○
○
○
Cross-circuit/ground fault in EMERGENCY STOP
circuit/no supply voltage
LEDs of the Power Stack Adapters
Table 8-2
LEDs of the Power Stack Adapters
LED
Color
Status
Description; cause
Remedy
PWR
-
Off
24 V power supply has failed or is too low
(< 14 V) or internal fuse defective.
Check input voltage.
If input voltage is > 18 V and LED off:
Return component for repair.
Red
Continuous
light
24 V power supply is available (>14 V);
internal board voltage fault.
Check input voltage.
If input voltage is > 18 V and LED red:
Return component for repair.
Green
Continuous
light
24 V power supply OK.
Internal board voltages OK.
--
Operation
8.5 Fault and system messages
SINAMICS GL150 6SL38503UM114PA0Z
98
Operating Instructions Rev.201910301420 MUSTER