8.4
Monitoring and protection functions
8.4.1
Safety shutdown of the converter
Tripping of the circuit-breaker in case of undervoltage
In the event of a serious fault, the converter is rapidly switched into a de-energized state by the
safety shutdown function.
The circuit-breaker must be equipped with an undervoltage trip to ensure the wire-break
protection for the circuit-breaker OFF command.
If a circuit-breaker OFF command is issued as a result of an overvoltage trip, the circuit-breaker
is switched off so that it is fail safe.
WARNING
Danger due to high voltages after a safety shutdown
In spite of a safety shutdown function, the drive may still be operational or high voltages may
still be present.
Residual voltages can result in death, severe injury or significant material damage. The
"Safety shutdown" function can neither ensure that the drive stops immediately nor can it
ensure that residual voltages do not still exist at the output terminals and within the unit.
● Make sure that the drive no longer rotates and that there are no high voltages present.
8.4.2
Speed monitoring with incremental encoder
Permanent speed monitoring enables motor control without an encoder. If higher-performance
applications require permanent speed monitoring, additional incremental encoders can be
connected to options A51 - A54. Higher-performance applications include, for example, closed-
loop position control or prolonged applications involving low speeds.
8.4.3
Uncontrolled stop, EMERGENCY STOP category 0
Function
This function concerns the stop category 0 EMERGENCY STOP for an uncontrolled stop in
accordance with EN 60 204-1. The function enables the voltage to be isolated via the circuit
breaker. The motor coasts down.
The safety shutdown is based on a single circuit. Protection against wire breakage is assured
due to the use of circuit breakers with undervoltage release. The emergency stop button used
is forced.
Operation
8.4 Monitoring and protection functions
SINAMICS GL150 6SL38503UM114PA0Z
96
Operating Instructions Rev.201910301420 MUSTER