9.5
Maintenance
9.5.1
Replacing a fan
NOTICE
Improper fan storage
Even if the fan is not used, the bearing grease ages. The utility of the fan can be impaired.
Rotate the fan at least once a year. Do not store the fan for longer than two years before
commissioning.
CAUTION
Injury caused by rotating fan
If the converter is equipped with a temperature-controlled fan, the fan can run on even if the
power section is switched off. You can be injured if you touch the fan.
● Wait until the fan has shut down.
For reliable operation, the fans must also be fitted with a monitoring device. Replace the fan in
good time to maintain the availability of the device.
Removing the fan
1. Disconnect the equipment.
2. Switch off the motor protection switch.
3. Remove the mesh cover on the junction box side of the fan. To do this, remove the seven
screws of the mesh cover.
4. Open the cover of the junction box and remove the fan cables.
5. The fan is attached to the roof section using four nuts, which are located inside the fan.
Remove the four nuts including the contact washers. If required, also remove the mesh
cover on the other side.
6. Lift the fan up and out. Eyebolts can be fitted on top of the fan so that it can be lifted out more
easily.
CAUTION
Injury due to a falling fan
The fans are very heavy (approx. 50 kg). If incorrectly handled, fans can fall and result in
injury and material damage.
● Take extra special care when lifting the fans.
Maintenance
9.5 Maintenance
SINAMICS GL150 6SL38503UM114PA0Z
110