05.2003
Technical Data
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
Operating Instructions
12-1
12 Technical
Data
EC Low-Voltage Directive
73/23/EEC and RL93/68/EEC
EN 50178
EC EMC Directive 89/336/EWG
EN 61800-3
EC Machinery Safety Directive
89/392/EEC
EN 60204-1
Approvals
UL / CSA
Type of cooling
Air-cooled with installed fan
Permissible ambient or coolant
temperature
•
During
operation
•
During
storage
•
During
transport
0° C to +45° C ( 32° F to 113° F)
(to 50° C, see fig. “Derating curves”)
-25° C to +55° C (-13° F to 131° F)
-25° C to +70° C (-13° F to 158° F)
Installation altitude
≤
1000 m above sea level (100 per cent loadability)
> 1000 m to 4000 m above sea level
(Loadability: see fig. “Derating curves”)
Permissible humidity rating
Relative air humidity
≤
95 % during transport and storage
≤
85 % in operation (condensation not
permissible)
Environmental conditions
to DIN IEC 721-3-3
Climate:
3K3
Chemically active substances: 3C2
Pollution degree
Pollution degree 2 to IEC 664-1 (DIN VDE 0110, Part 1),
Moisture condensation during operation is not permissible
Overvoltage category
Category III to IEC 664-1 (DIN VDE 0110, Part 2)
Type of protection
IP20 EN 60529
Protection class
Class 1 to EN 536 (DIN VDE 0106, Part 1)
Shock-hazard protection
EN 60204-1 and to DIN VDE 0106 Part 100 (VBG4)
Radio interference level
•
Standard
•
Options
According to EN 61800-3
No radio interference suppression
Radio interference suppression filter for class B1 or A1 to EN 55011
Noise immunity
Industrial sector to EN 61800-3
Paint
Indoor duty
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China