13-9
Number / Fault
Cause
Counter-measure
F065
Scom Telegram
No telegram was received at an Scom
interface (Scom/USS protocol) within the
telegram failure time.
Fault value r949:
1 = interface 1 (SCom1)
2 = interface 2 (SCom2)
- Check the connection CU -X100:1 to 5 and
check the connection PMU -X300.
- Check the connection CU -X103, or
X100/ 35,36 (Compact PLUS)
- Check "SCom/SCB TLG OFF" P704.01
(SCom1) and P704.02 (SCom2)
- Replace CU (-A10), or replace the unit
(Compact PLUS)
F070
SCB initialization fault
not Compact PLUS
A fault has occurred during initialization of the
SCB board.
Fault value r949:
1: Board code incorrect
2: SCB board not compatible
5: Error in configuration data
6: Initialization timeout
7: SCB board double
10: Channel error
F072
EB initialization fault
A fault has occurred during initialization of the
EB board.
Fault value r949:
2: 1st EB1 not compatible
3: 2nd EB1 not compatible
4: 1st EB2 not compatible
5: 2nd EB2 not compatible
21: Three EB1 boards
22: Three EB2 boards
110: Fault on 1st EB1
120: Fault on 2nd EB1
210: Fault on 1st EB2
220: Fault on 2nd EB2
F073
AnInp1SL1
not Compact PLUS
4 mA at analog input 1, slave 1 fallen short of
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 4, 5.
F074
AnInp2 SL1
not Compact PLUS
4 mA at analog input 2, slave 1 fallen short of
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 7, 8.
F075
AnInp3 SL1
not Compact PLUS
4 mA at analog input 3, slave 1 fallen short of
Check the connection of the signal source to
the SCI1 (slave 1) -X428: 10, 11.
F076
AnInp1 SL2
not Compact PLUS
4 mA at analog input 1, slave 2 fallen short of
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 4, 5.
F077
AnInp2 SL2
not Compact PLUS
4 mA at analog input 2, slave 2 fallen short of
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 7, 8.
F078
AnInp3 SL2
not Compact PLUS
4 mA at analog input 3, slave 2 fallen short of
Check the connection of the signal source to
the SCI1 (slave 2) -X428: 10, 11.