Typical circuits
A.1 Typical circuits for 3RM1 Standard
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
145
A.1.3
Direct-on-line starter 24 V DC with switch operation and 400 V brake
The current for the brake facility is drawn via two phases. Connection is via T1 and T3.
Make allowance for the additional current in the current setting value.
-S1 ON
-S2 Remote reset
Figure A-3 Direct-on-line starter 24 V DC with switch operation and 400 V brake