COMMISSIONING
6
87
8026508 / V1-0/2021-09|SICK
Subject to change without notice
O P E R A T I N G I N S T R U C T I O N S | VMS4300/5300
6.2.3
Assigning IP addresses
IP addresses in the delivery state:
Component
Default IP address
SIM2000 system controller
192.168.0.1
APU8520 dimensioning controller
192.168.0.100
LMS4x21 Master BG34
192.168.0.1
LMS4x21 Slave BG36
192.168.0.1
LMS4x21 Slave BG35
192.168.0.1
Tab. 16: Default IP addresses of device components
Recommended CAN and IP address assignments:
Component
CAN
TCP/IP
SIM2000 system controller
32
192.168.3.32
APU8520 dimensioning controller
9
192.168.3.100
LMS4x21 Master BG34
25
192.168.3.25
LMS4x21 Slave BG36
26
192.168.3.26
LMS4x21 Slave BG35
27
192.168.3.27
Tab. 17: Recommended addresses of device components
As the IP addresses are the same, the IP addresses must be assigned for each device
individually.
Fig. 76: Procedure for assigning IP addresses
▸
Make sure that the 2D LiDAR sensors are mounted correctly and electrically connected.
▸
Detach all Ethernet connections from the Ethernet switch so that only one 2D LiDAR
sensor is connected to the Ethernet switch.
▸
Connect the configuration PC to a free port on the Ethernet switch
▸
Make sure that the configuration PC is in the number range of the connected device
components.
▸
If it is not, change the IP address of the configuration PC accordingly.
Overview
Procedure