Table 3: Switching behavior of the door application diagnostic output
Actuator
Door application diagnostic output
Actuator not in response range
OFF
Actuator in response range
ON
Locking function application diagnostic output (Out AUX LOCK)
The signal of the locking function application diagnostic output changes as soon as the
locking function has been activated. This is not a safety output.
Table 4: Switching behavior of the locking function application diagnostic output
Locking function
Locking function application diagnostic output
Locking function active
ON
Locking function not active
OFF
Fault application diagnostic output (Out AUX DIA)
The signal of the fault application diagnostic output changes as soon as a fault occurs.
This is not a safety output.
Table 5: Switching behavior of the fault application diagnostic output
Fault
Fault application diagnostic output
Fault has occurred
ON
No fault
OFF
4.4.4
Switching behavior
Table 6: Switching behavior
Figure 13: Protective device
closed and locked
Figure 14: Protective device
closed but not locked
Figure 15: Protective device
open
Activating the locking func‐
tion
ON
OFF
Not relevant
OSSDs
ON
OFF
OFF
Out AUX LOCK
ON
OFF
OFF
Out AUX DOOR
ON
ON
OFF
4.4.5
Safe series connection
OSSDs of several safety locking devices can be connected by safe series connection.
The connected OSSDs act like the OSSDs of a single device.
PROJECT PLANNING
4
8023119/15LY/2019-10-28 | SICK
O P E R A T I N G I N S T R U C T I O N S | TR110 Lock
21