Technical Information
Chapter
3
RFH630
Electrical installation
8014957/YSU6/2016-01-08
©
SICK AG · Germany · All rights reserved · Subject to change without notice
37
3.7.12
Wiring the "External output 1" switching output in the CDB620-001 connection
module
Load (e.g. PLC)
GND
Quenching circuit:
Install an anti-surge
diode directly at the
load!
For inductive load:
V
out
RFH630
Serial Aux
(RS-232)
CDB620-001
U
IN
* = DC 10 V ... 30 V
CMC600
U
IN
*
The RFH630 indicates the switching status of its
logical "external output 1" via the serial Aux data
interface.
Software-controlled, the status is automatically
taken over by the CMC600 via the cable and
converted to the physical "Out 1" output in the
CDB620-001.
"External
output 1"
23
Out 1
22
GND
6
Shield
Ratings for "External output 1" ("Out 1“ switching output)
PNP switching against the supply voltage U
IN
*
[default setting: no function/disabled,
logic: not inverted (active high)]
– Short-circuit proof + temperature protected
– Galvanically not separate from U
IN
*
0 V ≤ V
out
≤ U
IN
*
U
IN
* − 1.5 V) ≤ V
out
≤ U
IN
* with I
out
≤ 100 mA
Switching
behavior
Features
Electrical
values