Operating Instructions
PBS
42
© SICK AG • Germany • All rights reserved • Subject to change without notice
8013154/U275/2010/02/01
SICK-specific
Index
(dezimal) Name Format
Access Range
Remark
70
OU2
8 Bit
enumerated
R/W
0 = „Hno“ : Hysteresis
mode (SP/RP) no
1 = „Hnc“ : Hysteresis
mode (SP/RP) nc
2 = „Fno“ : Window
mode (FH/HL) no
3 = „Fnc“ : Window
mode (FH/HL) nc
„no“ = „normally open“,
„nc“ = „normally closed"
72
UNIT
8 Bit
Enumeration
R/W
0 = bar
1 = MPa
2 = kPa
3 = PSI
4 = kg/cm²
This parameter defines the pressure measurement unit and the physical
unit of the local display. After setting this parameter the values for MBA
and MBE have to be read again since these values depend upon the
pressure unit.
73
HI
16 Bit
unsigned
R
0…10000
Maximum pressure that was applied at the pressure switch for diagnosis.
74
LO
16 Bit
unsigned
R
0…10000
Minimum pressure that was applied at the pressure switch for diagnosis.
77
DS2
16 Bit
unsigned
R/W
0…50000 (50s)
Switch-on delay of Q2 in ms.
78
DR2
16 Bit
unsigned
R/W
0…50000 (50s)
Switch-off delay of Q2 in ms.
80
DISP
8 Bit
Enumeration
R/W
0 = 1 Hz
1 = 2 Hz
2 = 5 Hz
3 = 10 Hz
Sets the refresh cycles of the display.
240
MBA
32 Bit IEEE 754
float
R
The process value “Pressure Value” is linearized such that a value of
1000 corresponds to the lower end of the measuring range (MBA) and
that a value of 9000 corresponds to the upper end of the measuring
range (MBE). Pressure values lower than the lower end of the measuring
range are transmitted as 0. Pressure values above the upper end of the
measuring range are transmitted as 10000.
241
MBE
32 Bit IEEE 754
float
R
The process value “Pressure Value” is linearized such that a value of
1000 corresponds to the lower end of the measuring range (MBA) and
that a value of 9000 corresponds to the upper end of the measuring
range (MBE). Pressure values lower than the lower end of the measuring
range are transmitted as 0. Pressure values above the upper end of the
measuring range are transmitted as 10000.
7. Starting, operation