Operating Instructions
PBS
40
© SICK AG • Germany • All rights reserved • Subject to change without notice
8013154/U275/2010/02/01
IO-Link-specific
Index
(dezimal) Name
Format
Access
Example
Range Remark
16
Vendor Name
R
SICK AG
Refer to IO-Link specification.
17
Vendor Text
R
Sensor
Intelligence
Refer to IO-Link specification.
19
ProductID
8 x 8Bit
R
6038664
Refer to IO-Link specification.
This SPDU refers to the corresponding IODD. It corre-
sponds to the virtual order number of the entire product
family.
21
Serial Number
8 x 8Bit
R
Production ID of the SICK pressure switch. It contains
alphanumeric characters.
24
Application Specific
Name
16 x 8Bit
R/W
The text can be defined by the user. It serves as identifica
-
tion of the pressure switch within a network.
33
Last Event
8Bit + 16Bit R
Refer to IO-Link specification.
40
ProcessDataIn
16Bit
R
This SPDU reflects the process data as they are also
cyclically transmitted (see above).
243
OrderNo
R
In contrast to the ProductID this SPDU refers to the actual
order number of the pressure switch.
SICK-specific
Index
(dezimal) Name Format
Access Range
Remark
65
SP1/
FH1
16 Bit
unsigned
R/W
1040-9000
Corresponds to the process value at which the switch is activated (closed,
Q +24 V) or to the upper limit in the window mode. In case of the output
being parametrized as „Hnc“ or „Fnc“ (normally closed), the logic is
inverted. The value of RP1 / FL1 shall be at least 40 units (0,5 % of the
measuring range) lower than the value of SP1 or FH1, respectively. If this
is not the case, RP1 or FL1 are set to the nearest possible value.
Service Data
7. Starting, operation