8013154/U275/2010/02/01
© SICK AG • Germany • All rights reserved • Subject to change without notice
41
Operating Instructions
PBS
SICK-specific
Index
(dezimal) Name Format
Access Range
Remark
66
RP1/
FL1
16 Bit
unsigned
R/W
1000-8960
Corresponds to the process value at which the switch is deactivated
(open, Q 0V) or to the lower limit in the window mode. In case of the
output being parametrized as „Hnc“ or „Fnc“ (normally closed), the logic
is inverted. The value of RP1 / FL1 shall be at least 40 units (0,5% of th
emeasuring range) lower than the value of SP1 or FH1, respectively. If this
is not the case, RP1 or FL1 are set to the nearest possible value.
67
OU1
8 Bit
Enumeration
R/W
0 = „Hno“ : Hysteresis
mode (SP/RP) no
1 = „Hnc“ : Hysteresis
mode (SP/RP) nc
2 = „Fno“ : Window
mode (FH/HL) no
3 = „Fnc“ : Window mode
(FH/HL) no
„no“ = „normally open“,
„nc“ = „normally closed".
68
SP2/
FH2
16 Bit
unsigned
R/W
1040-9000
Corresponds to the process value at which the switch is activated (closed, Q
+24V) or to the upper limit in the window mode. In case of the output being
parametrized as „Hnc“ or „Fnc“ (normally closed), the logic is inverted. The
value of RP2 / FL2 shall be at least 40 units (0,5% of the measuring range)
lower than the value of SP2 or FH2, respectively. If this is not the case, RP2
or FL2 are set to the nearest possible value.
75
DS1
16 Bit
unsigned
R/W
0…50000 (50s)
Switch-on delay of Q1 in ms.
76
DR1
16 Bit
unsigned
R/W
0…50000 (50s)
Switch-off delay of Q1 in ms.
69
RP2/
FL2
16 Bit
unsigned
R/W
1000-8960
Corresponds to the process value at which the switch is deactivated (open,
Q 0V) or to the lower limit in the window mode. In case of the output being
parametrized as „Hnc“ or „Fnc“ (normally closed), the logic is inverted. The
value of RP2 / FL2 shall be at least 40 units (0,5% of th emeasuring range)
lower than the value of SP2 or FH2, respectively. If this is not the case, RP2
or FL2 are set to the nearest possible value.
7. Starting, operation
7. Starting, operation