Electrical values
Input, teach-in (tch)
PNP: Teach = HIGH; Run = LOW
NPN: Teach = LOW; Run = HIGH
Input, all-teach-in (Atch), only for bus variants
PNP: Teach = HIGH; Run = LOW
NPN: Teach = LOW; Run = HIGH
Input, blanking input (bIn)
PNP: Blanked = HIGH; Free = LOW
NPN: Blanked = LOW; Free = HIGH
Input, light/dark (L--d)
PNP: Light switching = LOW; Dark switching = HIGH
NPN: Light switching = HIGH; Dark switching = LOW
5.3.2
Wiring the digital outputs
The number of digital outputs (open collector) available at the connections will vary,
depending on the device,
see "Pin assignment of the connections", page 16
. If the allo‐
cated event occurs in the read process, then the corresponding digital output is live.
In each case, the digital outputs are short-circuit protected and overcurrent protected.
Switching behavior: PNP
or
NPN
Electrical values
The sum current (100 mA) per sensor for all digital outputs is identical.
PNP/NPN residual voltage ≤ 1.8 V
Dielectric strength max 30 V
NOTE
When using sensors in bus operation, the sum current reduces as follows:
•
Up to 3 sensors = max. 100 mA
•
4-8 sensors = max. 50 mA
•
9-16 sensor = max. 20 mA
5.4
Connecting the supply voltage
NOTICE
Risk of damage to the device!
The device can become damaged if it is connected to a voltage supply that is already
switched on.
•
Only connect the device when the supply cable is de-energized.
The device must be connected to a power supply unit with the following properties:
•
Supply voltage DC 10.8 V – 26.4 V (SELV/PELV as per currently valid standards)
•
Electricity source with at least 3 W power
ELECTRICAL INSTALLATION
5
8023304.11XV/2018-11-29 | SICK
O P E R A T I N G I N S T R U C T I O N S | KTL180