6.2.6
Process data outputs
The output data has a length of 262 bytes.
Byte
Module
Description
0 … 5
Standard I/O ports
Process data outputs on standard inputs
1)
6 … 37
IO-Link port 0
Process data outputs on IO-Link port 0
2)
38 … 69
IO-Link port 1
Process data outputs on IO-Link port 1
2)
70 … 101
IO-Link port 2
Process data outputs on IO-Link port 2
2)
102 … 133
IO-Link port 3
Process data outputs on IO-Link port 3
2)
134 … 165
IO-Link port 4
Process data outputs on IO-Link port 4
2)
166 … 197
IO-Link port 5
Process data outputs on IO-Link port 5
2)
198 … 229
IO-Link port 6
Process data outputs on IO-Link port 6
2)
230 … 261
IO-Link port 7
Process data outputs on IO-Link port 7
2)
1)
→
See Page 28, Chapter Table 22.
2)
→
See Page 28, Chapter Table 23.
Table 21: Process data output
Standard output data
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Description
0
O32
O34
O22
O24
O12
O14
O02
O04
Output data
O04: Output on port 0, pin 4
In order to use this function
on an I/O port, the port must
be configured as an output.
1
O72
O74
O62
O64
O52
O54
O42
O44
2
R32
R34
R22
R24
R12
R14
R02
R04
Restart
Output is restarted after a
short-circuit is identified
3
R72
R74
R62
R64
R52
R54
R42
R44
4
0
0
0
0
0
0
0
0
Reserved
5
0
0
0
0
0
DL
GO
RO
Display control
• DL: Display locked, PLC lock
• GO: Green display LED lights
up
• RO: Red display LED lights
up
Table 22: Standard output data
IO-Link output data
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Description
6 … 37
IO-Link port 1 output data
Table 23: IO-Link output data