Operating instructions IO-Link Master IOLG2EI-03208R01 – EtherNet/IP™
System integration and configuration
24
© SICK AG • Presence Detection • Subject to change without notice • 8018483
6.2.3
Module configuration
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Description
0
P3
P2
P1
P0
Port function
• 0x00: Standard I/O
• 0x01: IO-Link
1
P7
P6
P5
P4
Table 15:
Module configuration
6.2.4
IO-Link port configuration
The following setup is the same for all IO-Link ports, but the relevant byte
offset for the chosen port must be noted.
→
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Description
2
Basis
Time
Cycle time
Note the following section from
the IO-Link specification V1.1.2
(July 2013).
3
Validation type
Validation type:
• 0: No validation
• 1: Compatible (VID + DID)
• 2: Identical
(VIS + DID + ser. no.)
4
VID 1 (MSB)
Vendor ID
5
VID 2 (LSB)
6
DID 1 (MSB)
Device ID
7
DID 2
8
DID 3 (LSB)
9 … 24
Serial number 1 (MSB) … serial number 16 (LSB)
Serial number
25
Parameter server
Parameter server:
• 0x8X: Enable
• 0x0X: Disable
• 0x40: Clear
• 0xX1: Upload enable
• 0xX2: Download enable
Table 16:
IO-Link port configuration, example using port 0
Extract from the IO-Link specification
V1.1.2 (July 2013)
Time base
Multiplier
Bit 7
Bit 0