Excessive current load
WARNING!
Equipment damage due to excessive current load!
An excessive current load may result in damage to the
equipment.
• Do not exceed the maximum permissible total current
of 8 A for the IO-Link Master.
• Each output provides a maximum current of 2 A.
• The sensors/bus and actuators should be powered via
separate current sources if possible.
Incorrect functional grounding
WARNING!
Incorrect functional grounding!
An incorrect functional grounding may result in equip-
ment damage or malfunction.
• The grounding between the IO-Link Master and the
machine must be a low-impedance system.
• The ground connection must be as short as possible.
5.2
IO-Link Master electrical connection
1.
Ensure power supply is not connected.
2. Connect the IO-Link Master to the functional grounding of the system
using the supplied ground strap. See next page.
3.
Connect supply voltage to “POWER IN” using a suitable cable.
4. Connect fieldbus connection via EIP1/EIP2.
5.
Connect IO-Link devices or standard devices to the IO-Link ports.
6.
If provided, connect the next gateway to “POWER OUT”.
Functional grounding
Fig. 4: Ground connection