WARNING
There is a risk of death or serious injury as diagnostics for the protective device are not
reliable.
In the event that position data that is not plausible or other safety-critical faults are
detected, the non-safe process controller must request the safe state by deactivating
both test signals.
Time requirements for test signals
The difference in time between the test signals from the process controller and the
movement status detected by the OLM 100 Hi sensors must not be more than
0.75 seconds.
NOTE
There may be availability issues if accelerations are less than 60 mm/s
2
. In this case,
the test signals can be delayed by as much as 650 ms.
Technical requirements
Technical data on the inputs can be found in the operating instructions for the Flexi Soft
controller.
6.4.2
SSI interface
The position value of OLM 1 is provided to the process controller via the SSI interface.
The process controller interface can either be an SSI master or an SSI listener. On that
basis, the SSI interface must be configured accordingly on the MOC module.
If the process controller is an SSI master, the MOC module must function as an SSI lis‐
tener.
If the process controller is an SSI listener, the MOC module must function as an SSI
master.
Requirements for the process controller SSI interface
The requirements for the SSI interface vary depending on the sensor unit in use.
Table 12: Requirements for the sensor unit with part number 1087575
Parameter
Requirement
Protocol frame
24 position data bits +1 error bit
Data decoding
Binary
Transmission rate (SSI master only)
100 kBaud ... 400 kBaud
Table 13: Requirements for the sensor unit with part number 1090629
Parameter
Requirement
Protocol frame
31 position data bits +1 error bit
Data decoding
Binary
Transmission rate (SSI master only)
100 kBaud ... 400 kBaud
If the process controller operates its SSI interface as a master, data packets must be
transmitted cyclically every 0 ms to 8 ms.
In order to guarantee that diagnostics are reliable, the transmission rates of the two SSI
interfaces must be set to different values. The interface for OLM 2 is set to 167 kBaud.
The process controller SSI interface requires a 120 ohm terminator.
ELECTRICAL INSTALLATION
6
8020941/12O9/2019-08-05 | SICK
O P E R A T I N G I N S T R U C T I O N S | Safe Linear Positioning
29