Diagnostics
The device transmits error states in various ways. If a connected module detects a
fault, this is transmitted in the corresponding “Error information” process date.
In addition, the class
Gateway Configuration
0x64 in attribute 105 contains the code of
the last error to occur. The following table shows possible errors:
Last Gateway Error (0x64 0x69)
Description
0x0206
Number of connected modules changed during
operation.
0x0107
Invalid module connected to gateway.
0x0108
The assignment of the connected modules is
wrong (see chapter 7.4).
If the WI180C-EN is integrated in an Allen Bradley control system, certain error mes‐
sages may occur whose message texts cannot be clearly assigned. The following error
messages come from the RSLogix 5000 software.
Error code
Message
Possible cause
16#0108
Connection Request Error: Con‐
nection Type (Multicast/Unicast)
not supported.
Check whether the configuration assembly
(instance 100) is activated. If it is, check
whether the configuration data within it is cor‐
rect and has been fully configured.
16#0114
Electronic Keying Mismatched:
Electronic keying product code
and/or vendor ID mismatched.
Check whether the incorrect EDS file has per‐
haps been selected.
16#0127
Connection Request Error:
Invalid output size.
Check whether the correct communication for‐
mat is being used for the control. The control's
default value is
Data DINT
. The WI180C-EN
needs the
Input Data DINT
communication for‐
mat.
16#0204
Connection Request Error: Con‐
nection timed out.
Check the supply voltage at the WI180C-EN.
Check the Ethernet cables of the WI180C-EN
for interruptions.
Check whether the IP address of the WI180C-
EN matches the IP address stored in the con‐
trol. Possible causes: Following a restart, the
WI180C-EN has lost the IP address assigned
to it (
see "IP address of the WI180C-EN",
8
DIAGNOSTICS
40