NOTE
•
You select the I/O assembly as the Connection under Module Properties.
•
In principle, several connections can be established from the control to the
WI180C-EN . However, the data provided via the WI180C-EN is fundamentally
restricted. The WI180C-EN will reject connections once the limit has been
reached. In this case, the WI180C-EN outputs the following error codes:
°
01h = general error code
°
0113h = extended error code
Table 19: I/O assemblies
Content
Data type
Assembly
101
102
103
104
Switching signals Q1 of all modules
UINT-16
x
x
-
-
Switching signals Q2 of all modules
UINT-16
-
x
-
-
Switching signals Q3 of all modules
UINT-16
-
x
-
-
Error status of all modules
UINT-16
-
x
-
-
Measured value of all modules
ARRAY[16] OF
UINT-16
-
-
-
x
Teach command for all modules
UINT-16
-
-
x
-
Confirm errors for all modules
UINT-16
-
-
x
-
7.7.2
I/O assemblies with process data
7.7.2.1
Switching signals
Table 20: Q1
Access
Data type
Description
R
UINT-16
This part of the instance transmits the first switching signal
Q1 of all connected modules
Table 21: Q2
Access
Data type
Description
R
UINT-16
This part of the instance transmits the second switching sig‐
nal Q2 of all connected modules
Table 22: Q3
Access
Data type
Description
R
UINT-16
This part of the instance transmits the third switching signal
Q3 of all connected modules and/or the status of the exter‐
nal input of all connected modules (function depends on
module)
Table 23: Error status
Access
Data type
Description
R
UINT-16
This part of the instance transmits the error status of all con‐
nected modules
7.7.2.2
measured values
Table 24: Transmission of measured values
Contents
Format
Byte
Type
Measured value Slot0 UINT-16
0
Lowest-order byte
1
Highest-order byte
7
OPERATION
24
O P E R A T I N G I N S T R U C T I O N S | WI180C-EN
8024950/2019-11-04 | SICK