Manual of SR258 intelligent controller
42
PDIS
7d
0-30d
1d
Time
section
of
disinfection
monitoring
DDIS
10min
1-180
1min
Heating time of disinfection
TDIS
70
o
C
0-90
o
C
1
o
C
Temperature of disinfection
SDIS
18:00
00:00-21:00 1:00
Start time of disinfection
Function setting
►Press “▲”, “OTDI” displays on the screen
►Press “SET”, “OTDI OFF” display
►Press “SET”, “OFF” blinks
►Press “▲/▼”, to activate this function, “OTDI ON” displays
►Press “SET” or “ESC” to save the setting
►Press “▲”, “PDIS 7” displays
►Press “SET”, “7” blinks
►Press “▲/▼”, to adjust the days for disinfection monitoring,
►Press “SET” or “ESC” to save the setting
►Press “▲”, “DDIS 10Min” displays on the screen
►Press “SET”, “10” blinks
►Press “▲/▼”, to adjust the heating time of disinfection
►Press “SET” or “ESC” to save the setting
►Press “▲”, “TDIS 70
o
C” displays on the screen
►Press “SET”, “70
o
C” blinks
►Press “▲/▼”, to adjust the temperature of disinfection
►Press “SET” or “ESC” to save the setting
►Press “▲”, “SDIS 18:00” displays on the screen
►Press “SET”, “18” blinks
►Press “▲/▼”, to adjust the start time of the disinfection
►Press “SET” or “ESC” to save the setting
7.10 FS Flow rate monitoring and pump dry running protection
Function description:
In order to achieve this function, an extra digital flow meter FRT should be installed on the
return pipe of solar system, when solar pump R1 is triggered, the flow rate of return pipe is
monitored to ensure system runs normally.
If relay R1 is powered, if controller hasn’t got signal from digital flow meter within 30 seconds,
then solar pump R1 will be stopped, error message will appear, and sign will