Manual of SR288 intelligent controller
28
CFRF
5
℃
-39-9
℃
0.5
℃
Switch-off temperature
of anti-freeze function
OTCO
Tube collector function
TCST
07:00
00:00-23:00
1min
Start time of tube
collector function
TCEN
19:00
00:00-23:00
1min
Stop time of tube
collector function
TCRU
30s
30-300s
1s
Pump runtime during
tube collector function
TCIN
30min
5-60min
1min
Pump stop time during
tube collector function
Function setting:
OCEM (Collector emergency shutdown function) setup
►Select “COL” function menu
►Press “SET”, “OCEM” displays on the screen
►Press “SET” again, “OCEM ON” displays on the
screen
►Press “SET”, “ON” blinks on the screen
(If it is necessary to shut down this function, press “▲/▼” to deactivate it)
►Press “SET” or “ESC” to save the setting
►Press “▲”, “OCEM 130
o
C” displays on the screen
►Press “SET”, “130
o
C” blinks on the screen
►Press “▲/▼”, to activate or deactivate the collector emergency function
►Press “SET” or “ESC” to save the setting
►Press “ESC” to return to the previous menu
OCCO (Collector cooling function) setup
►Press “▲”, “OCCO” displays on the screen
►Press “SET”, “OCEM OFF” displays on the screen
►Press “SET”, “OFF” blinks on the screen
►Press “▲/▼”, to activated this function, “OCEM ON” displays on the screen
►Press “▲”, “CMAX 110
o
C” displays on the screen
►Press “▲/▼”, to adjust the switch-on temperature of collector cooling function
►Press “SET” or “ESC” to save the setting