Manual of SR288 intelligent controller
23
Speed control
If the temperature reaches or exceeds the switch-on temperature difference, the pump
switches on at 100% speed for 10s. Then, the speed is reduced to the minimum pump speed
value.
If the temperature difference reaches the preset temperature difference, the pump speed
increases by one step (10%). The response of the controller can be adapted via the
parameter RIS. If the difference increases by the adjustable rise value RIS, the pump speed
increases by 10% until the maximum pump speed of 100% is reached. If the temperature
difference decreases by the adjustable rise value (RIS), pump speed will be decreased by
one step 10% accordingly.
Note:
To enable speed control function, the corresponding pump type has to be set to
(MIN, MAX) and relay control has to be set to (PULS, PSOL, PHEA or 0-10 V) (under
adjustment menu PUMP).
SMX Maximum tank temperature protection set
If the tank temperature reaches the adjusted maximum temperature, the tank will no longer
be loaded in order to avoid damage caused by overheating. If the maximum tank
temperature is exceeded, sign is displayed on the screen.
The sensor for tank maximum limitation (SMAX) can be selected. The maximum limitation
always refers to the sensor selected (T2 or T3). The switch-on hysteresis (HYST) is
selectable(Default is 2
o
C), for example, when tank maximum temperature is set to 70
o
C
,
then
at 68
o
C, Maximum tank temperature protection function is deactivated automatically.