39
10.3 Auxiliary Function Setting Mode 2
To enter Auxiliary Function Setting Mode 2, press and hold the UP, DOWN and MODE keys (in that
order) together for approx. 3 seconds in PV/SV Display Mode.
Character
Factory Default
Setting Item, Function, Setting Range
Input type
(Table 10.3-1)
Character
Input Range
Character
Input Range
K -200 to 1370
K -320 to 2500
K -200.0 to 400.0
K -200.0 to 750.0
J -200 to 1000
J -320 to 1800
R 0 to 1760
R 0 to 3200
S 0 to 1760
S 0 to 3200
B 0 to 1820
B 0 to 3300
E -200 to 800
E -320 to 1500
T -200.0 to 400.0
T -200.0 to 750.0
N -200 to 1300
N -320 to 2300
PL-
0 to 1390
PL-
0 to 2500
C(W/Re5-26) 0 to 2315
C(W/Re5-26) 0 to 4200
Pt100 -200.0 to 850.0
Pt100 -200.0 to 1000.0
JPt100 -200.0 to 500.0
JPt100 -200.0 to 900.0
Pt100 -200 to 850
Pt100 -300 to 1500
JPt100 -200 to 500
JPt100 -300 to 900
4-20 mA DC -2000 to 10000 (Externally mounted 50
shunt resistor)
0-20 mA DC -2000 to 10000 (Externally mounted 50
shunt resistor)
0-1 V DC -2000 to 10000
0-5 V DC -2000 to 10000
1-5 V DC -2000 to 10000
0-10 V DC -2000 to 10000
4-20 mA DC -2000 to 10000 (Built-in 50
shunt resistor)
0-20 mA DC -2000 to 10000 (Built-in 50
shunt resistor)
Scaling high limit
• Setting range: Scaling low limit to Input range high limit (*)
Scaling low limit
• Setting range: Input range low limit to Scaling high limit (*)
Decimal point place
•
: No decimal point
: 1 digit after decimal point
: 2 digits after decimal point
: 3 digits after decimal point
PV filter time constant
• Setting range: 0.0 to 10.0 sec
A1 type
•
: No alarm action
: High limit alarm
: Low limit alarm
: High limit with standby alarm
: Low limit with standby alarm
(*) The placement of the decimal point follows the selection or input range.