5.5 Maintenance Mode
To enter Maintenance mode, press the
UP
and
FAST keys
(in that order) together for approx. 5 seconds
in PV/SV Display Mode.
If the unit enters Maintenance mode, all outputs are forced to turn OFF.
Character
Factory Default
Setting Item, Function, Setting Range
A1 output ON/OFF
• A1 output can be turned ON by the UP key, and OFF by the DOWN key.
Not available if No alarm action is selected in [A1 type].
•
: Output OFF
: Output ON
A2 output ON/OFF
• A2 output can be turned ON by the UP key, and OFF by the DOWN key.
Not available if No alarm action is selected in [A2 type].
Not available if Insulated power output (P24 option or P5 option) is ordered.
•
: Output OFF
: Output ON
A3 output ON/OFF
• A3 output can be turned ON by the UP key, and OFF by the DOWN key.
Not available if No alarm action or High/Low limit range alarm is selected in
[A3 type].
•
: Output OFF
: Output ON
A4 output ON/OFF
• A4 output can be turned ON by the UP key, and OFF by the DOWN key.
Available when Alarm 4 output (A4 option) is ordered.
Not available if No alarm action is selected in [A4 type].
•
: Output OFF
: Output ON
Transmission output 1 manual output
• Sets output amount of Transmission output 1.
• Setting range: 0.0 to 100.0%
Transmission output 2 manual output
• Sets output amount of Transmission output 2.
Available when Transmission output 2 (T
□
2 option) is ordered.
• Setting range: 0.0 to 100.0%