20
Character
Factory Default
Setting Item, Function, Setting Range
A4 type
• Selects an A4 type. See Section 7.1 (p.27).
Available when Alarm 4 output (A4 option) is ordered.
• If A4 type is changed, A4 value will default to 0 (0.0).
•
: No alarm action
:
High limit alarm
: Low limit alarm
: High limit with standby alarm
: Low limit with standby alarm
: High/Low limit range alarm [See Section 7.3 (p.28).]
A1 Energized/De-energized
• Selects A1 Energized/De-energized.
Not available if No alarm action is selected in [A1 type].
• When [A1 Energized] is selected, A1 output (terminals 7, 8) is conducted (ON)
while A1 action indicator is lit.
A1 output is not conducted (OFF) while A1 action indicator is unlit.
When [A1 De-energized] is selected, A1 output (terminals 7, 8) is not conducted
(OFF) while A1 action indicator is lit.
A1 output is conducted (ON) while A1 action indicator is unlit.
A1 output will be substituted by A2, A3 or A4 output.
A1 output terminals will be substituted by A2, A3 or A4 output terminals as follows.
A2 output terminals: 9, 10
A3 output terminals: 12, 13
A4 output terminals: 15, 16
High limit alarm (Energized)
High limit alarm (De-energized)
(Fig. 5.4-1)
(Fig. 5.4-2)
•
: Energized
: De-energized
A2 Energized/De-energized
• Selects A2 Energized/De-energized.
Not available if No alarm action is selected in [A2 type].
Not available if Insulated power output (P24 option or P5 option) is ordered.
•
: Energized
: De-energized
A3 Energized/De-energized
• Selects A3 Energized/De-energized.
Not available if No alarm action or High/Low limit range alarm is selected
in [A3 type].
•
: Energized
: De-energized
OFF
ON
A1 value
A1 hysteresis
OFF
ON
A1 value
A1 hysteresis