Character
Factory Default
Setting Item, Function, Setting Range
Transmission output 2 low limit
• Sets the Transmission output 2 low limit value.
Available when Transmission output 2 (T
□
2 option) is ordered.
4-20 mA DC
Equals 4 mA DC output.
0-20 mA DC
Equals 0 mA DC output.
0-1 V DC, 0-5 V DC,
0-10 V DC
Equals 0 V DC output.
1-5 V DC
Equals 1 V DC output.
• Setting range: Input range low limit to Transmission output 2 high limit (The
placement of the decimal point follows the selection or input range.)
Event input function
• Selects Event input function.
Not available if Serial communication (C5 option) is ordered.
•
(HOLD):
PV at the given time is held and indicated by closing Event input terminals (14,
17). The HOLD function is cancelled by opening the Event input terminals (14,
17).
(Peak HOLD):
The updated maximum PV is indicated by closing Event input terminals (14, 17).
The Peak HOLD function is cancelled by opening the Event input terminals
(14, 17).
(Bottom HOLD):
The updated minimum PV is indicated by closing Event input terminals (14, 17).
The Bottom HOLD function is cancelled by opening Event input terminals
(14, 17).
(Alarm HOLD 1):
If any of [A1 HOLD function] to [A4 HOLD function] is set to “Enabled”, and if the
alarm is ON, the alarm will be maintained by closing Event input terminals (14,
17).
The Alarm HOLD function will be cancelled by opening Event input terminals
(14, 17). While the Event input terminals (14, 17) are open, the Alarm HOLD
function will be disabled.
(Alarm HOLD 2):
If any of [A1 HOLD function] to [A4 HOLD function] is set to “Enabled”, and if the
alarm is ON, the alarm will be maintained by opening the Event input terminals
(14, 17).
The Alarm HOLD function will be cancelled by closing Event input terminals (14,
17). While the Event input terminals (14, 17) are closed, the Alarm HOLD
function will be disabled.
A1 HOLD function
• Enables/Disables the A1 HOLD function.
Not available if No alarm action is selected in [A1 type].
• If A1 HOLD function is set to “Enabled”, and if the alarm is ON, the alarm output
ON status will be maintained until the following is conducted.
• The FAST key is pressed for approx. 3 seconds.
• The power is turned OFF.
• The HOLD is cancelled by the Event input function.
During A1 HOLD, the A1 action indicator flashes.
•
: Disabled
: Enabled