Character
Factory Default
Setting Item, Function, Setting Range
A4 Energized/De-energized
• Selects A4 Energized/De-energized.
Available only when Alarm 4 output (A4 option) is ordered.
Not available if No alarm action is selected in [A4 type].
•
: Energized
: De-energized
A1 hysteresis
• Sets A1 hysteresis.
• Not available if No alarm action is selected in [A1 type].
• Setting range: 0.1 to 100.0
( )
Direct current, DC voltage input: 1 to 1000 (The placement of the decimal point
follows the selection.)
A2 hysteresis
• Sets A2 hysteresis.
• Not available if No alarm action is selected in [A2 type].
Not available if Insulated power output (P24 option or P5 option) is ordered.
• Setting range: 0.1 to 100.0
( )
Direct current, DC voltage input: 1 to 1000 (The placement of the decimal point
follows the selection.)
A3 hysteresis
• Sets A3 hysteresis.
• Not available if No alarm action or High/Low limit range alarm is selected
in [A3 type].
• Setting range: 0.1 to 100.0
( )
Direct current, DC voltage input: 1 to 1000 (The placement of the decimal point
follows the selection.)
A4 hysteresis
• Sets A4 hysteresis.
• Available only when Alarm 4 output (A4 option) is ordered.
Not available if No alarm action is selected in [A4 type].
• Setting range: 0.1 to 100.0
( )
Direct current, DC voltage input: 1 to 1000 (The placement of the decimal point
follows the selection.)
A1 delay time
• Sets A1 action delay time.
When setting time has elapsed after the input enters the alarm output range, the
alarm is activated.
Not available if No alarm action is selected in [A1 type].
• Setting range: 0 to 9999 seconds
A2 delay time
• Sets A2 action delay time.
When setting time has elapsed after the input enters the alarm output range, the
alarm is activated.
• Not available if No alarm action is selected in [A2 type].
Not available if the Insulated power output (P24 option or P5 option) is ordered.
• Setting range: 0 to 9999 seconds