12. Specifications
12.1 Standard Specifications
Mounting method
:
Flush
Setting
method
: Input system using membrane sheet key
Display
PV display: 11-segment backlight LCD Red/Green/Orange, character size 12.0 x 5.4 mm (H x W)
SV display:
11-segment backlight LCD Green, character size 6.0 x 3.5 mm (H x W)
MEMO display: 11-segment backlight LCD Green, character size 4.8 x 2.8 mm (H x W)
Indicators:
Backlight
Orange
Accuracy (Setting and Indication)
:
Thermocouple:
Within
0.2% of each input span 1digit, or within 2 (4 ),
whichever
is
greater
However R, S input, 0 to 200 (32 to 392 ): Within 6 (12 )
B input, 0 to 300 (32 to 572 ): Accuracy is not guaranteed
K, J, E, T, N input, less than 0 (32 ): Within 0.4% of input span 1digit
RTD:
Within
0.1% of each input span 1digit, or within 1 (2 ),
whichever is greater
Direct
current:
Within
0.2% of each input span 1digit
DC
voltage:
Within
0.2% of each input span 1digit
Input sampling period
: 250ms
Input
Thermocouple: K, J, R, S, B, E, T, N, PL- , C (W/Re5-26)
External resistance, 100 or less
(However, B input: External resistance, 40 or less)
RTD: Pt100, JPt100, 3-wire system
Allowable input lead wire resistance (10 or less per wire)
Direct current: 0 to 20mA DC, 4 to 20mA DC
Input impedance: 50
Allowable input current: 50mA or less
DC voltage:
0 to 1V DC Input impedance (1M or more)
Allowable input voltage (5V DC or less)
Allowable signal source resistance (2k or less)
0 to 5V DC, 1 to 5V DC, 0 to 10V DC Input impedance (100k or more)
Allowable input voltage (15V DC or less)
Allowable signal source resistance (100 or less)
Control output OUT1
Relay contact: 1a, Control capacity: 3A 250V AC (resistive load)
1A 250V AC (inductive load cos =0.4)
Electrical life: 100,000 cycles
Non-contact voltage (For SSR drive): 12V DC 15%, Maximum 40mA (short circuit protected)
Direct current: 4 to 20mA DC, Load resistance, Maximum 550
Alarm 1 output
Action: ON/OFF action
Hysteresis:
0.1 to 100.0 ( ) (Default: 1.0 )
DC voltage, current inputs: 1 to 1000 (The placement of the decimal point
follows the selection.)
Output: Relay contact 1a
Control capacity: 3A 250V AC (resistive load)
Electrical life: 100,000 cycles