13
6.3 Setup Mode
To enter Setup mode, press and hold the
and
keys (in that order) together for approx. 3
seconds in PV/SV display mode.
Character
Name, Function, Setting range
Default value
Input type
K (-200 to 1370 )
• The input type can be selected from thermocouple (10 types), RTD (2 types), DC
current (2 types) and DC voltage (4 types), and the unit / can be selected as well.
• When changing the input from DC voltage to other inputs, remove the sensor connected
to this controller first, then change the input. If the input is changed with the sensor
connected, the input circuit may break.
•
(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC differs from
that of 0 to 1V DC.
(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC: 9
(+) side input terminal number of 0 to 1V DC: 10
K -200 to
1370
K
-320 to 2500
K
-200.0 to 400.0
K
-320.0 to 750.0
J
-200 to 1000
J
-320 to 1800
R
0 to 1760
R
0 to 3200
S
0 to 1760
S
0 to 3200
B
0 to 1820
B
0 to 3300
E
-200 to 800
E
-320 to 1500
T
-200.0 to 400.0
T
-320.0 to 750.0
N
-200 to 1300
N
-320 to 2300
PL-
0 to 1390
PL-
0 to 2500
C(W/Re5-26)
0 to 2315
C(W/Re5-26)
0 to 4200
Pt100 -200.0 to
850.0
Pt100
-320.0 to 1500.0
JPt100
-200.0 to 500.0
JPt100
-320.0 to 900.0
Pt100
-200 to 850
Pt100
-320 to 1500
JPt100
-200 to 500
JPt100
-320 to 900
4 to 20mA DC
-2000 to 10000
0 to 20mA DC
-2000 to 10000
0 to 1V DC
-2000 to 10000
0 to 5V DC
-2000 to 10000
1 to 5V DC
-2000 to 10000
0 to 10V DC
-2000 to 10000
Scaling high limit
1370
• Sets scaling high limit value.
• Setting range: Scaling low limit value to input range high limit value
DC voltage, current inputs: -2000 to 10000 (The placement of the decimal point follows the selection.)
Scaling low limit
-200
• Sets scaling low limit value.
• Setting range: Input range low limit value to scaling high limit value
DC voltage, current inputs: -2000 to 10000 (The placement of the decimal point follows the selection.)
Decimal point place
No decimal point
• Selects decimal point place.
Available only for DC voltage, current inputs
•
: No decimal point
: 1 digit after decimal point
: 2 digits after decimal point
: 3 digits after decimal point