18
[Alarm action Energized/De-energized]
When [Alarm Energized (
)] is selected, the alarm output (terminals 3 and 4, or 5 and 6) is
conductive (ON) while the alarm output indicator is lit.
The alarm output is not conductive (OFF) while the alarm output indicator is not lit.
When [Alarm De-energized (
)] is selected, the alarm output (terminals 3 and 4, or 5 and 6) is
not conductive (OFF) while the alarm output indicator is lit.
The alarm output is conductive (ON) while the alarm output indicator is not lit.
High limit alarm (when Energized is set) High limit alarm (when De-energized is set)
A1: Alarm 1
(Fig. 6.3-2)
(Fig. 6.3-3)
For Alarm 2(A2), read “A2” for “A1”.
[Contact input function selection]
Actions differ depending on the selection in [OUT/OFF key function] in Setup mode.
• When
Control output OFF function
(
) is selected in [OUT/OFF key function]
(Table 6.3-1)
Connecting terminal No.
Contact input function
17 and 18
(DI1-COM)
16 and 18
(DI2-COM)
Set value memory
external selection
(
)
OUT/OFF external
selection 1
(
)
OUT/OFF external
selection 2
(
)
Open Open
SV
SV
SV
Closed Open
SV2
SV2
Open Closed
SV3
Control output OFF
Control output OFF
Closed Closed
SV4
• When
Auto/Manual control
(
) is selected in [OUT/OFF key function]
(Table 6.3-2)
Connecting terminal No.
Contact input function
17 and 18
(DI1-COM)
16 and 18
(DI2-COM)
Set value memory
external selection
(
)
OUT/OFF external
selection 1
(
)
OUT/OFF external
selection 2
(
)
Open
Open
SV
SV (Automatic control)
SV (Automatic control)
Closed
Open
SV2
SV2 (Automatic control)
Open
Closed SV3
Manual control
Manual control
Closed Closed
SV4
OFF
ON
A1 hysteresis
SV
+ A1 value
OFF
ON
SV
+ A1 value
A1 hysteresis