12
6. Setup
Setup (setting the Input type, Alarm type, Control action, etc.) should be done before using this controller,
according to the user’s conditions.
Default values: Input (K, -200 to1370 ), Alarm 1 (No alarm action), Reverse (Heating) action
If the user’s specification is the same as the default value of the ACS-13A, it is not necessary to set up the
controller. Proceed to Section “7. Settings”.
6.1 Turn the Power Supply to the ACS-13A ON
.
After the power is turned on, the PV display indicates the input type, and the SV display indicates the
input range high limit value (thermocouple, RTD inputs) or scaling high limit value (DC voltage, current
inputs) for approximately 3 seconds. (Table 6.1-1)
During this time, all outputs and the indicators are in OFF status.
Control will then start, indicating the PV (process variable) on the PV display and SV (desired value) on the
SV display.
While control output OFF function is working, the PV display indicates
.
(Indication depends on the selection in [Output status when input errors occur].
(Table 6.1-1)
Sensor input
PV display SV display
PV display
SV display
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
0 to 5V DC
1 to 5V DC
0 to 10V DC
Scaling high limit value
6.2 Basic Key Operations
To enter each setting mode, refer to respective setting modes.
To set or select each setting item, use the
or
key, then register the value with the
key.
•
If the
key is pressed for 3 seconds in any setting mode, the unit will return to PV/SV
display mode.