14
SV
OUT2 proportional band
Air cooling
Oil cooling
Water cooling
Character
Name, Function, Setting range
Default value
PV filter time constant
0.0 seconds
• Sets PV filter time constant.
If the value is set too high, it affects control results due to the delay of response.
• Setting range: 0.0 to 10.0 seconds
OUT1 high limit
100%
• Sets the high limit value of OUT1.
Not available if OUT1 is in ON/OFF control
• Setting range: OUT1 low limit value to 100%
(Direct current output type: OUT1 low limit value to 105%)
OUT1 low limit
0%
• Sets the low limit value of OUT1.
Not available if OUT1 is in ON/OFF control.
• Setting range: 0% to OUT1 high limit value
(Direct current output type: -5% to OUT1 high limit value)
OUT1 ON/OFF hysteresis
1.0
• Sets ON/OFF hysteresis for OUT1.
Available only when OUT1 is in ON/OFF control
• Setting range: 0.1 to 100.0 ( ), DC voltage, current inputs: 1 to 1000 (The placement
of the decimal point follows the selection.)
OUT2 cooling method
Air cooling
• Selects OUT2 action from air, oil and water cooling.
Available if the D
option is ordered.
Not available if OUT2 is in ON/OFF control.
•
: Air cooling (linear characteristic)
: Oil cooling (1.5th power of the linear characteristic)
: Water cooling (2nd power of the linear characteristic)
(Fig. 6.3-1)
OUT2 high limit
100%
• Sets OUT2 high limit value.
Available if the D
option is ordered.
Not available if OUT2 is in ON/OFF control.
• Setting range: OUT2 low limit value to 100%
OUT2 low limit
0%
• Sets OUT2 low limit value.
Available if the D
option is ordered.
Not available if OUT2 is in ON/OFF control.
• Setting range: 0% to OUT2 high limit value
Overlap band/Dead band
0.0
• Sets the overlap band or dead band for OUT1 and OUT2.
+ Set value: Dead band, –Set value: Overlap band
Available when the D
option is ordered
• Setting range: -100.0 to 100.0 ( ), DC voltage, current inputs: -1000 to 1000 (The
placement of the decimal point follows the selection.)
OUT2 ON/OFF hysteresis
1.0
• Sets ON/OFF hysteresis for OUT2.
Available when the D
option is ordered and when OUT2 is in ON/OFF control
• Setting range: 0.1 to 100.0 ( ), DC voltage, current inputs: 1 to 1000 (The placement
of the decimal point follows the selection.)