5-4. Remote Control
The equipment incorporates a Remote Control receptacle.
Remote control box is an optional part.
Remote Control operation is available by connecting the compatible Remote
Controller to the receptacle.
5-5. Earth Leakage Relay and Grounding
Danger: Electric Shock
Ground the grounding terminal to the earth as set out in the manual.
Failure to do so could result injury.
Even though all the load terminals have been grounded to the earth, the
canopy grounding terminal should also be grounded to the earth.
Grounding should be made whilst the engine is stopped.
Whenever the earth leakage relay has been activated, you should always
repair the fault before re-using the machine.
The equipment is provided with an earth leakage relay (ELR) with in the Main
Circuit Breaker (MCB) to detect any earth leakage due to problems such as
insulation failure of the load whilst the generator is running. When activated ELR
will automatically switch the MCB to the OFF position.
The specifications of the earth leakage relay:
Rated Sensitive Current: 30mA (or below)
(Grounding resistance: 500
Ω
or below)
(1) Grounding Work
A qualified electrician should perform the grounding work at the 2 points
(500
Ω
or below).
The Canopy of this equipment (canopy grounding terminal)
The Canopy of the load
<Caution>
In the event you cannot ground
the generator to the earth,
consult with our dealer or
authorized distributor.
CANOPY
GROUNDING
TERMINAL
GROUNDING
ROD
REMOTE CONTROL RECEPTACLE
REMOTE CONTROL BOX