15
(2) Oil Pressure / Water Temp / Speed Monitor
Displays the engine speed, water temperature and oil pressure. Switching the selector switch
changes the display in the following order: Speed
Water temp
Oil press.
Engine speed is
displayed first, when the engine is started.
Speed
Displays the engine speed. 1800rpm is displayed at 60 Hz.
Water Temp
Displays the temperature of the engine coolant. Normal
temperature displayed during operation should generally
between 167°F (75
℃
) and 194°F (90
℃
) depend on the
usage.
< Note >
If the coolant temperature exceeds above 212 °F(100
℃
)
, immediately stop all connected
equipment to the generator, and idle the engine while cool down the coolant temperature.
Oil Press
Displays the pressure of the engine lubrication system. Normal pressure displayed during
operation should generally between 28 and 64 psi (2.00 – 4.40 x 100 kPa) depend on the
usage. However, the pressure may rise above this range just after starting a cold engine.
Idle the engine until it reaches the normal pressure.
(3) Fuel Level
It shows the amount of fuel in the tank. All lamps are lit when the amount reaches to the
maximum level, and FULL is lit. The lit lamp decreases as the amount of fuel in the tank
reaches to EMPTY. The fuel level on the control panel will only display the fuel level for the
internal fuel tank.
Generator Meters and Gauges
(1) Voltmeter
The voltmeter displays the three-phase output
voltage (voltage between L1-L3). Check that 240 V
is displayed during operation. Output voltage for
single-phase three-wire (voltage between U-W) is
the same voltage as the three-phase output voltage
(voltage between L1-L3). Accordingly, use the voltage meter displayed value as a reference.
(2) Ammeter
Displays the output current (phase current) of the generator. Turn the ammeter selector switch
to “L1+U” to display the output current of the three-phase L1 phase and single-phase U phase.
Turn the switch to “L3+W” to display the output current of the three-phase L3 phase and
single-phase W phase. “L2” displays the output current of three-phase output terminal L2.
< Note >
If measuring the output current for a single-phase three-wire type, turn the ammeter selector
switch to “L1+U” or “L3+W”. The voltage cannot be accurately measured if set to “L2”.
(3) Frequency Meter
Displays the frequency of the power source. Check that 60 Hz is displayed during operation.
Oil Press
Water Temp
Speed
Fuel Level
Selector
Switch