9-2. Voltage Switching Function
WARNING : ELECTRIC SHOCK
If performing any electric voltage switching, turn all breakers to OFF position
and stop operation.
Lock the generator using a padlock to be operated by designated operators
only.
CAUTION : PROPERTY DAMAGE
Check that the voltages of the generator output setting, output terminal
connection and load power source are consistent.
Turn the circuit breakers on the operation panel to OFF and stop operation.
Turn the lever of the voltage selector switch to the desired output setting.
Three-phase 480/208-V and Single-phase 240/120-V power is output to the
main terminal board
. Refer to section “
7-2. Connecting Load Cables
”.
Start the engine and turn the circuit breakers to ON to transmit power to the
main terminal board.
Push
Padlock
3 Phase
480V
3 Phase
208V
1 Phase
240 / 120V
Starter switch
Throttle switch
Circuit breakers
1
1
2
3
4