20
TOTAL 16/20kVA
(
16/20kW
)
TOTAL 16/20kVA
(
16/20kW
)
< Note >
When connecting a load, check that the generator output setting, output terminal connection
position, and load power source are all matching.
If using the O terminal, be careful that the currents of each phase are uniform.
Use proper tools when connecting a load to sufficiently tighten the connection. Failure
to sufficiently tighten the connection will result in cable burnout.
(1) 3-Phase Output Terminal
For 3-phase load:
Terminal voltage is 400/440 V [200/220 V] (50/60Hz).
* The values in brackets are for when set to 200/220V.
For 1-phase load:
Terminal voltage is 230/254 V [115/127 V] (50/60Hz).
* The values in brackets are for when set to 200/220V.
For 1-phase load:
Terminal voltage is 400/440 V [200/220 V] (50/60Hz).
* The values in brackets are for when set to 200/220V.
Total output capacity
Unit
3-phase load
1-phase load
Total
R-S-T
R-O,S-O,T-O
R-S,S-T,T-R
kVA
20/25
6.7/8.3
11.5/14.4
20/25
kW
16/20
6.7/8.3
11.5/14.4
16/20
Load
R
S
T
O
20/25kVA
(
16/20kW
)
R
S
T
O
Load
Load
Load
R
S
T
O
Load
Load
Load