12 

12. Countermeasure against Noise

12-1. Noise Filter & Condition for CE Marking

 

 

˚

  Noise Filter 

Frequency components of noise generated by the thyristors are distributed in the 
areas of a few megahertz or lower. Universal noise filters available on the market 

do not have sufficient effect to reduce such noise. 

It is possible to reduce such noise when the following our designated noise filter is 
used. 

The filter is specified for use in our thyristor power regulators. 
 

 
 

 

˚

 Condition for CE Marking 

 

CAUTION

 

When the product is used with noise filter and wired as specified by the instruction manual, the product meets the requirement of EMC command. 

 

 

1. For dealing with EMC command

 

Use in combination with a noise filter designed by us. Install the noise filter on the same metal plate as the PAC27. Do not forget to properly 

ground it. 
The length of wiring between the noise filter and the PAC27 should be 0.5m or less. 

 

2. For dealing with low-voltage command 

When power line is wired, as a precaution against accidental short-circuit, make sure to install one molded case circuit breaker for each PAC27. 
The current capacity of a molded case circuit breaker should be 1.3 times lower than that of the PAC27. 

 

 

 

12-2. Power Waveform Distortion Improvement by Power Capacitor

 

To connect a power capacitor for power-factor improvement across the main terminals R and T of the PAC27 is an effective method to improve 

power distortion (higher harmonics). 
The effect is recognized at a rate of 1μF capacitor capacity to about 1A current capacity. 

 
Although the method is simple, attention should be paid to the following points: 

1. Close attention should be paid to the rated current of the capacitor and a rise in temperature since a higher harmonic current flows into the 

capacitor. 

2. The capacitor may produce higher harmonic voltage through its resonance with the power supply line inductance. Check the power waveforms. 

 

 

 
 
 

 

Type

 

Current capacity 

NF2030C-SDG 

30A 

NF2050C-SDG 

45A 

NF2060C-SDG 

60A 

NF2080C-SDG 

80A 

NF2100C-SDG 

100A 

Manufacturer: Soshin Denki K.K 

Summary of Contents for PAC27

Page 1: ...to get into the product If something gets in by mistake and it is necessary to insert your hand or tool inside it make sure to turn the power off and to confirm that the condition are safe enough to...

Page 2: ...2YHUKHDWLQJ ODUP 7K ULVWRU 7URXEOH ODUP 3RZHU GMXVWPHQW DQG 6RIW 6WDUW 7LPH GMXVWPHQW QWHUQDO 3RZHU 5HJXODWLRQ 6RIW 6WDUW 7LPH GMXVWPHQW 9DULRXV KDUDFWHULVWLFV XUUHQW DSDFLW DQG DORULILF 9DOXH PELHQW...

Page 3: ...3 1 Confirmation of Specification Codes Please double check that the delivered product is exactly as you specified If you need further information please get in touch with our nearest local office...

Page 4: ...er adjuster SOFT START Soft start time adjuster HEATER SET Heater setting device for heater break alarm option H B SET Heater break alarm setting device option Terminal marking and description C1 C2 C...

Page 5: ...perature which exceeds 40 C Temperature allowed for this instrument is below 50 C 2 Humidity which exceeds 90 RH 3 Flammable gas corrosive gas or gas or particles that can deteriorate electrical insul...

Page 6: ...as to keep it from easy contact with persons It has to be installed vertically for heat radiation leaving more than 100 mm spaces above and below it respectively If it is inevitable to install the in...

Page 7: ...7 6 Circuit Block Diagram and Terminal Marking Terminal Marking Control Terminal No 1 18 See Page 4 2 2 Power Load Circuits...

Page 8: ...ity When T terminals are wired use wire material of 0 5 mm2 minimum 8 Wiring for Control Signals For control signals M3 5 terminal screws are used Use a crimp style terminal of more than 3 5 mm in ins...

Page 9: ...d temperature blocks the gate signal of the thyristor and stops output at which time current flows across the alarm output terminals AL1 and AL2 The monitor lamp O H lights The normal state is restore...

Page 10: ...fect of suppressing the rush current of a heater Setting is possible from less than one second min to more than 30 seconds max The longer the set time the slower the response of output Time should be...

Page 11: ...In case ambient temperature exceeds 50 C the instrument should be used with load current as illustrated below 11 3 Control System and Output Waveform 11 4 Special Heater and Feedback Control Type of h...

Page 12: ...dealing with low voltage command When power line is wired as a precaution against accidental short circuit make sure to install one molded case circuit breaker for each PAC27 The current capacity of...

Page 13: ...h a thyristor In case an ordinary transformer is used no problem will be caused when the load rate is held below 70 of the rating for the transformer 13 2 When Electromagnetic Switch Contactor Is Used...

Page 14: ...operation manual power adjuster switch is used voltage current input type 14 1 4 External power Base residual power adjuster 14 1 5 Contact input High low power adjuster When an external power adjust...

Page 15: ...ssumption that voltage and current have similar waveforms Depending on the types of loads however voltage has a waveform which is different from or out of proportion to that of current If this is the...

Page 16: ...sed for almost all types of heaters and allows for precision control of temperature As the constant power control is meant for a heater load a correct power level is unable to be attained for other lo...

Page 17: ...imiting works at 0 of the rated current and no output is produced If the instrument is used without the current limit setting device the control terminals CL2 and CL3 have to be short circuited Then t...

Page 18: ...m with no condensation Storage temperature between 20 and 65 C Applicable standards Safety IEC 60947 4 EN60947 4 EMC EN60947 4 EMC immunity EN60947 4 on condition that designated noise filter is used...

Page 19: ...ne load circuit This sometimes happens during trial run 3 Base power or low power regulator is connected It is for preventing minimum value of output from being 0 Detach low power regulator and rechec...

Page 20: ...Specialists Head Office 2 30 10 Kitamachi Nerima ku Tokyo 179 0081 Japan Phone 81 3 3931 7891 Fax 81 3 3931 3089 E MAIL exp dept shimaden co jp URL http www shimaden co jp The contents of this manual...

Reviews: