background image

16 

14-3. Various Feedback Functions

 

The PAC27 has various feedback functions (constant voltage (standard), constant current, constant power, power linearity), which are so easy to 

operate since an external CT or PT need not be attached. 
The feedback control functions detect thyristor current or voltage internally in the regulator and control it to a value set by a control signal from 

the controller or some other means. 
If line voltage or the load varies, a change in output can be held to a minimum. The functions are most suitable for load characteristic compensation 

and precision control. 

 

14-3-1. Constant voltage (VFB: voltage feedback) control (standard)

 

This function is equipped on a standard basis. Output voltage corresponding to a control input signal is obtained as a true effective value. 
The function is usable for almost all types of loads but requires the current limiting function (option) in the case of a load with a large rush current. 

 

14-3-2. Constant current (CFB: current feedback) control

 

Output current corresponding to a control input signal is obtained. When the load changes, this function works to keep output current at a constant 

level by changing output voltage. It is used for heaters in which rush current is large and/or current fluctuates violently. It is also effective in 
stabilizing load current. Even for pure metal heaters with large rush current, the use of the current control function (option) is not required. Because 

current corresponding to a control input signal is tried to output, a power regulator is used for regulation if the capacity of the PAC27 does not 

match with that of the heater. 
 

14-3-3. Constant power (PFB: power feedback) control

 

Output power, i.e., a calorific value from the heater, which corresponds to a control input signal is obtained. Since it is assumed that the 

function is used against a load of variable resistance, rated voltage x rated current x 1/2 is set as a 100% value of power. The function is 

capable of being used for almost all types of heaters and allows for precision control of temperature. 
As the constant power control is meant for a heater load, a correct power level is unable to be attained for other loads (such as a motor) 

than heaters. 
Selection of this control system for an SiC heater makes compensation for heater deterioration possible without using a tap change 

transformer for the heater. (This may not be possible due to certain relationships between line voltage and heater voltage.) 
 

Example: When the line voltage is 200 V AC and the rated current of an SiC heater is 140 V 20A (2.8 kW): 

The rated voltage of the thyristors x rated current x 1/2 is set as a 100% power value, that is, 2.8 (kW) x 2/200 (V) = 28(A). 

Therefore, a PAC27 of 200-220 V 30A should be selected. 

In this case the 100% power value is 220 (V) x 30 (A) x 1/2 = 3.3 (kW). In order to match with the heater power, the power 
regulator should be tightened to 2.8 (kW)/3.3 (kW)=85%. Owing to this, at 100% of input control signal, the initial value of the 

heater attains 140V 20A (2.8 kW). When the heater deteriorates to raise the resistance value, it can be used at 200 V 14A (2.8 
kW) maximum. During this period, output power corresponding to control input is obtained without requiring any other operation 

such as tap changing by a transformer. 

 

14-3-4. Power linearity (VVFB: voltage square feedback) control

 

It is arranged so that the square of output voltage corresponds to constant resistance. 
Since power against constant resistance is in proportion to the square of voltage, power corresponding to control signals is obtained when used 

for constant resistance heaters (nickel chrome, iron chrome, etc.). 
Although the controllability is lower when compared to constant power control since resistance inevitably changes between a few percent and ten 

percent or so in actual heaters, power which is substantially in proportion to control input signals may be obtained.  It cannot be obtained by 
ordinary constant voltage control. 

It is a type of constant voltage control. Unlike constant power control, it does not require calculation of the capacities of the PAC27 and the heater. 

Installation of a power regulator is also unnecessary. 

 

 

Summary of Contents for PAC27

Page 1: ...to get into the product If something gets in by mistake and it is necessary to insert your hand or tool inside it make sure to turn the power off and to confirm that the condition are safe enough to...

Page 2: ...2YHUKHDWLQJ ODUP 7K ULVWRU 7URXEOH ODUP 3RZHU GMXVWPHQW DQG 6RIW 6WDUW 7LPH GMXVWPHQW QWHUQDO 3RZHU 5HJXODWLRQ 6RIW 6WDUW 7LPH GMXVWPHQW 9DULRXV KDUDFWHULVWLFV XUUHQW DSDFLW DQG DORULILF 9DOXH PELHQW...

Page 3: ...3 1 Confirmation of Specification Codes Please double check that the delivered product is exactly as you specified If you need further information please get in touch with our nearest local office...

Page 4: ...er adjuster SOFT START Soft start time adjuster HEATER SET Heater setting device for heater break alarm option H B SET Heater break alarm setting device option Terminal marking and description C1 C2 C...

Page 5: ...perature which exceeds 40 C Temperature allowed for this instrument is below 50 C 2 Humidity which exceeds 90 RH 3 Flammable gas corrosive gas or gas or particles that can deteriorate electrical insul...

Page 6: ...as to keep it from easy contact with persons It has to be installed vertically for heat radiation leaving more than 100 mm spaces above and below it respectively If it is inevitable to install the in...

Page 7: ...7 6 Circuit Block Diagram and Terminal Marking Terminal Marking Control Terminal No 1 18 See Page 4 2 2 Power Load Circuits...

Page 8: ...ity When T terminals are wired use wire material of 0 5 mm2 minimum 8 Wiring for Control Signals For control signals M3 5 terminal screws are used Use a crimp style terminal of more than 3 5 mm in ins...

Page 9: ...d temperature blocks the gate signal of the thyristor and stops output at which time current flows across the alarm output terminals AL1 and AL2 The monitor lamp O H lights The normal state is restore...

Page 10: ...fect of suppressing the rush current of a heater Setting is possible from less than one second min to more than 30 seconds max The longer the set time the slower the response of output Time should be...

Page 11: ...In case ambient temperature exceeds 50 C the instrument should be used with load current as illustrated below 11 3 Control System and Output Waveform 11 4 Special Heater and Feedback Control Type of h...

Page 12: ...dealing with low voltage command When power line is wired as a precaution against accidental short circuit make sure to install one molded case circuit breaker for each PAC27 The current capacity of...

Page 13: ...h a thyristor In case an ordinary transformer is used no problem will be caused when the load rate is held below 70 of the rating for the transformer 13 2 When Electromagnetic Switch Contactor Is Used...

Page 14: ...operation manual power adjuster switch is used voltage current input type 14 1 4 External power Base residual power adjuster 14 1 5 Contact input High low power adjuster When an external power adjust...

Page 15: ...ssumption that voltage and current have similar waveforms Depending on the types of loads however voltage has a waveform which is different from or out of proportion to that of current If this is the...

Page 16: ...sed for almost all types of heaters and allows for precision control of temperature As the constant power control is meant for a heater load a correct power level is unable to be attained for other lo...

Page 17: ...imiting works at 0 of the rated current and no output is produced If the instrument is used without the current limit setting device the control terminals CL2 and CL3 have to be short circuited Then t...

Page 18: ...m with no condensation Storage temperature between 20 and 65 C Applicable standards Safety IEC 60947 4 EN60947 4 EMC EN60947 4 EMC immunity EN60947 4 on condition that designated noise filter is used...

Page 19: ...ne load circuit This sometimes happens during trial run 3 Base power or low power regulator is connected It is for preventing minimum value of output from being 0 Detach low power regulator and rechec...

Page 20: ...Specialists Head Office 2 30 10 Kitamachi Nerima ku Tokyo 179 0081 Japan Phone 81 3 3931 7891 Fax 81 3 3931 3089 E MAIL exp dept shimaden co jp URL http www shimaden co jp The contents of this manual...

Reviews: